Pipe Marking

ANSI/ASME A13.1 2007 Standard

Color Chart

FLAMMABLE Black on Yellow e.g.: Hydrogen

COMBUSTIBLE White on Brown e.g.: Canola Oil

TOXIC/CORROSIVE Black on Orange e.g.: Nitric Acid

FIRE QUENCHING White on Red e.g.: Fire Water

OTHER WATER White on Green e.g.: Boiled Water

COMPRESSED AIR White on Blue e.g.: Nitrogen

Defined by User
White on Black
White on Gray
White on Purple
Black on White

Pipe Marker Placement

Label placement in relation to point of normal approach

Size Chart

Outside pipe diameter w/ cover:

75" - 1.25"
1.5" - 2"
2.5" - 6"
8" - 10"
Over 10"

Minimum Length field color

8"
8"
12"
24"
32"

Min. letter height

.5"
.75"
1.25"
2.5"
3.5"

  • Adjacent to changes in direction
  • Adjacent to all valves & flanges
  • Both sides of floor/wall penetrations
  • Every 25' 50' on straight runs is typical